Yfn18-24kv Series Indoor AC Hv Load Break Switch
Basic Info
Model No.: YFN18-24/630-20
Product Description
Model NO.: YFN18-24/630-20 Certification: ISO9001-2008, Ce, SGS Test Equipment: IEC Standard Trademark: YF Operation Model: Manual or Electrical Operation Arc Extinction Principle: Air-Compressing Environment: Indoor High Voltage Origin: Jiangyin Yunfeng, China YFN18-24kV
Product Overivew
YFN18-24kV series indoor AC HV load switch is manufactured according to ABB's technology. It works under the air-compressing arc extinction principle.Beacuse of its unique structural design, it can make full use of the air-compression extinguishing arc generated in the tripping process of switch. It is applied in the HV AC 12kV network with the frequency of 50HZ for opening, closing the load current, overload current and making the short-circuit current. Together with the HV current-limiting Fuse and trip device, it combines YFN18-24R series indoor AC HV load switch-fuse combination unit, which can reliably disconnect the rated short-circuit current.
Model Specification
Service Conditions
1.Altitude≤1000m;
2.Ambient temperature-25ºC-+ 40ºC;
3.The daily average of relative humidity shall not be larger than 95% and the monthly average shall not be larger than 90%:
4.The ambient air shall not be subject to the obvious pollution such as corrosive or combustible gas and steam;
5.The site without fire hazards and explosion hazards;
6.The site that the seismic intensity does not exceed degree 8; the gradient shall not exceed 5°
Main Technology Parameters
Contact us if you need more details on load break switch. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Switchgear、Air-Compressing Arc Extinction Principle. If these products fail to match your need, please contact us and we would like to provide relevant information.
Product Overivew
YFN18-24kV series indoor AC HV load switch is manufactured according to ABB's technology. It works under the air-compressing arc extinction principle.Beacuse of its unique structural design, it can make full use of the air-compression extinguishing arc generated in the tripping process of switch. It is applied in the HV AC 12kV network with the frequency of 50HZ for opening, closing the load current, overload current and making the short-circuit current. Together with the HV current-limiting Fuse and trip device, it combines YFN18-24R series indoor AC HV load switch-fuse combination unit, which can reliably disconnect the rated short-circuit current.
Model Specification
Service Conditions
1.Altitude≤1000m;
2.Ambient temperature-25ºC-+ 40ºC;
3.The daily average of relative humidity shall not be larger than 95% and the monthly average shall not be larger than 90%:
4.The ambient air shall not be subject to the obvious pollution such as corrosive or combustible gas and steam;
5.The site without fire hazards and explosion hazards;
6.The site that the seismic intensity does not exceed degree 8; the gradient shall not exceed 5°
Main Technology Parameters
Serial No. | Item | Unit | YFN18-24 HV Load Switch |
1 | Rated voltage | kV | 24 |
2 | Rated frequency | Hz | 50 |
3 | Rated current | A | 630 |
4 | Rated active load breaking current | A | 630 |
5 | Rated closed loop breaking current | A | 630 |
6 | 5% rated active load breaking current | A | 31.5 |
7 | Cable charging current | A | 10 |
8 | 1min power-frequency withstand voltage(effective value) to earth, phase-to-phase/isloating fracture | kV/kV | 65/79 |
9 | Lightning impulse withstand voltage(peak)to earth,phase-to-phase/isolating fracture | kV/kV | 125/145 |
10 | Rated short-time withstand current(thermal stability current)/duration | kA/s | 20/3 |
11 | Rated short-time withstand current(thermal stability current)/duration of Earthing switch | kA/s | 20/2 |
12 | Rated peak withstand current(dynamic stability current) | kA | 50 |
13 | Rated short-circuit making current(peak) | kA | 50 |
14 | Rated short-circuit breaking current(current-limiting fuse) | kA | --- |
15 | Rated transfer current | A | --- |
16 | Time of switch opening triggered by breaking of fuse | ms | --- |
17 | Impact output energy at breaking of fuse | J(Joule) | --- |
18 | Opening closing operation torque of load switch | Nm | 80 |
19 | Opening closing operation torque of earth switch | Nm | 35 |
20 | Mechnical life | Time | 2000 |
21 | Phasing spacing | mm | 275 |
Contact us if you need more details on load break switch. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Switchgear、Air-Compressing Arc Extinction Principle. If these products fail to match your need, please contact us and we would like to provide relevant information.
Product Categories : 24kV Indoor HV load switch
Other Products
Hot Products
YFZRN-24 AC Hv Vacuum Load Switch with Safe and Easy FuseFn5-12r (T) D Indoor AC Hv Load Switch-Fuse Combination Unitout Door Load Switch for ABB CabinetOrignal Hot Sale out Door Isolating Switch for 1250Aout Door Three Position Spring Load SwitchHot Sale out Door Circuit Breaker for Oumaout Door Circuit Breaker Mechanism for High Pressure CabinetParts of Electrical Control Panel Low Voltage Switchgear11kV Parts of Vacuum Circuit Breaker8PT CrankKEMA Testified Medium Voltage Switchgear Epoxy Resin SensorIndustrial Control Panel Genset Control Panel Electrical SwitchgearWecome Group Power Distribution Equipment Series Type SF6 Ring Main UnitMNS Control Cubicle Switch CabinetKYN28 24kV Metal Enclosed Medium Voltage Withdrawable Switchgear PanelMedium Voltage VS1 Indoor 11kV Vacuum Circuit Breaker