High Quality 24kV Indoor HV Load Switch, Load Break Switch, 24kv Indoor High-Voltage Load Switch Suppliers in China

Home > Products > 24kV Indoor HV load switch > Reasonable Price for 24kv Indoor Use High-Voltage Isolating Switch-Yfgn-24

Reasonable Price for 24kv Indoor Use High-Voltage Isolating Switch-Yfgn-24

Basic Info

Model No.:  YFGN-24/630

Product Description

Model NO.: YFGN-24/630 Structure: Three-column Disconnector Operation: Manual or Electric Number of Poles: Three Pole Structure of Operating: Electric Trademark: YF Type: High-voltage Installation: Indoor High-Voltage Grounding Mode: Grounding Series: Three Certification: ISO, CE, ISO9001 Origin: Jiangyin Yunfeng, China Product Overview
YFGN-24/630 indoor AC HV disconnector is applied at the site with rated voltage of 24kV and rated frequency of 50Hz. It is a switch with obvious safe isolating fracture designed and developed independently according to GB3804, guaranteeing the system safety accordingly. Such model of disconnector has features of small size, simple but reasonable structure, small operation force, reliable performance and convenient maintenance, ect. It can be use with 24kV HV Circuit Breaker in the cabinet and it is a HV disconnector with advantageous cost performance.


Reasonable Price for 24kv Indoor Use High-Voltage Isolating Switch-Yfgn-24          Reasonable Price for 24kv Indoor Use High-Voltage Isolating Switch-Yfgn-24



Model Specification
Reasonable Price for 24kv Indoor Use High-Voltage Isolating Switch-Yfgn-24
Note: The sensor with live display can be used for the switch insulator.

Characteristics
         a.small size
         b.simple but reasonable structure
         c.small operation force
         d.reliable performance 
         e.convenient maintenance


Reasonable Price for 24kv Indoor Use High-Voltage Isolating Switch-Yfgn-24
Service Conditions
          1.Altitude:2000m;
          2.Ambient temperature-25ºC-+ 40ºC;
          3.The daily average of relative humidity shall not be larger than 95% and the monthly average shall not be               larger than 90%:
          4.The ambient air shall not be subject to the obvious pollution such as corrosive or combustible gas and                   steam;
          5.The site without fire hazards and explosion hazards;
          6.The site that the seismic intensity does not exceed degree 8; the gradient shall not exceed 5°

Main Technical Parameters
  Serial No. Item Unit Disconnector
1 Rated voltage kV  24
2 Rated frequency Hz 50
3 Rated current A 630
4 Rated peak withstand current kA 63
5 Rated short-time withstand current(4 seconds) kA 25
6 1min power-frequency withstand voltage(effective value) to earth, phase-to-phase/isloating fracture kV/kV 65/79
7 Full-wave lightning impulse withstand voltage(peak)to earth,phase-to-phase/isolating fracture kV/kV 125/145
8 Main loop resistance μΩ ≤50
9 Phase-to-phase center distance mm 275±3 or 250±3
10 Open distance of isolation contact knife switch mm ≥200
11 Maximum manual operation torque N ≤200
12 Three-phase opening and closng asynchronization ms ≤1

Reasonable Price for 24kv Indoor Use High-Voltage Isolating Switch-Yfgn-24                Reasonable Price for 24kv Indoor Use High-Voltage Isolating Switch-Yfgn-24

Contact us if you need more details on Isolating switch. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Indoor High-Voltage、Load Break Switch. If these products fail to match your need, please contact us and we would like to provide relevant information.

Product Categories : 24kV Indoor HV load switch

Email to this supplier
  • *Subject:
  • To:

  • *Messages:
    Your message must be between 20-8000 characters