High Quality Indoor HV Isolating switch, Load Break Switch, High-Voltage Isolating Switch Suppliers in China

Home > Products > Indoor HV Isolating switch > Indoor Hv Disconnecting Switch-Yfgn35-40.5, Easy Operation, Reliable Price

Indoor Hv Disconnecting Switch-Yfgn35-40.5, Easy Operation, Reliable Price

Basic Info

Model No.:  YFGN35-40.5/630

Product Description

Model NO.: YFGN35-40.5/630 Structure: Three-column Disconnector Operation: Manual Number of Poles: Three Pole Series: Three Certification: ISO, CE, ISO9001 Features: Small Size, Easy Installation,Ect Origin: Jiangyin Yunfeng, China Type: High-voltage Installation: Indoor High-Voltage Grounding Mode: Not Grounding Grounding: Un Grounded Structure of Operating: Electric Application: 35kv Box Substation Trademark: YF 1.Product Overview
YFGN-40.5 series isolation switch is used in the network with A.C50Hz,rated voltage 40.5kv are self-researched and manufactured by the company according to standards of GB3804-2004 and GB16926-1997, designed especially for 35kv box substation. It can also be use in power system as an independent electric unit. This product is featured by small size, easy installation, simple operation with scientific and national structure, flexible and reliable and obvious isolated fracture.

2.Model Specification
Indoor Hv Disconnecting Switch-Yfgn35-40.5, Easy Operation, Reliable Price

3.Applicable environment
1. Altitude is not more than 1000m 
2. Ambient air temperature comes to -25ºC~+40ºC
3. Relative humidity: daily average value is not more than 95%;
4. Ambient air shall not clearly polluted by air dust, corrosive or flammable gas, vapor, or salt spray, etc
5. In the secondary system, inductive electromagnetic amplitude value shall not be more than 1.6kv

4. Structure and Principle
1. Basic structure mainly composed of frame, isolation switch. Isolation knife, vacuum arc extinguishing chamber are fixed on frame with isolator. Operation mode is side operation. Operation Mechanism drives main shaft of switch, main shaft rotates and drives vacuum arc extinguishing chamber or isolation knife to act with crutch through insulation operation bar, realizing the switch knife opening and closing operation.
See Fig.1 and Fig.2 for outline and installation dimension of combined electric appliance 
2. Work principle
Switching on and off operation for isolation knife .

5.Main Technical Parameters
Serial No. Item Unit Isolating switch
1 Rated voltage  kV 40.5
2 Rated current A 1250,630
3 Rated frequency Hz 50
4 Rated peak withstand current kA 50
5 Rated short-time withstand current(4s) kA 20
6 1 min power-frequency withstand voltage(effective value) to earth,phase-to-phase/isolating fracture kV/kV 95/115
7 Full wave lightning impluse withstand voltage(peak)  to earth,phase-to-phase/isolating fracture kV/kV 185/215
8 Main loop resistance μΩ ≤120
9 Center distance between phases mm 410±2
10 Clearance between open contacts mm 19±1
11 Manual maximum operating torque N ≤90
12 Three-phase opening and closing asynchronization ms ≤1



 

Contact us if you need more details on Switchgear. We are ready to answer your questions on packaging, logistics, certification or any other aspects about High Voltage、Disconnecting switch. If these products fail to match your need, please contact us and we would like to provide relevant information.

Product Categories : Indoor HV Isolating switch