High Quality Vacuum Circuit Breaker, 10kv Vacuum Circuit Breaker, Air Insulated Cabinet Circuit Breaker Suppliers in China

Home > Products > VGK series > VGK circuit breaker > VGK Series Indoor High Voltage Vacuum Circuit Breaker used in Air insulated cabinet

VGK Series Indoor High Voltage Vacuum Circuit Breaker used in Air insulated cabinet

Product Description

Liyond

VGK Series Indoor High Voltage Vacuum Circuit Breaker used in Air insulated cabinet 

Product display

VGK Series Indoor High Voltage Vacuum Circuit Breaker used in Air insulated cabinet 

VGK-I-12 series indoor high voltage AC Vacuum Circuit Breaker

Summary

VGK-I-12 series indoor high voltage AC Vacuum circuit breaker (vertical rotary isolation type) is an Indoor Switchgear for 12kV power system. It is used as protection and control unit for power grid equipment and industrial and mining enterprises. The nature of the load and frequent operation, multiple occasions of short-circuit current. The product adopts the new Circuit breaker Operating Mechanism, the vacuum interrupter and the main conductive circuit parts are solidly sealed in one part to protect the arc extinguishing chamber from collision, dust and condensation. The environment adaptability is strong, the operation and maintenance cost is greatly reduced, and the product is realized once. Partially maintenance-free, the operating mechanism is less maintenance; the operating mechanism is integrated with the Circuit Breaker and the Isolating switch. It has been tested by type test and has E2 electrical life and M2 mechanical life.

Main Technical Specification

No. Parameters name Unit Parameters

 

 

Circuit breaker Load switch
1 Rated voltage kV 12
2 Rated current of main busbar A 630 1250
3 Rated frequency Hz 50
4 Rated short time withstand current Main circuit kA 25 31.5
Ground circuit 21.7 27.4
5 Rated short-time peak current Main circuit 63 80
Ground circuit 54.5 68.5
6 Rated short circuit withstand time Main circuit s 4
Ground circuit 2
7 Rated short circuit closing current (peak) kA 63 80
8 Rated short circuit breaking current 25 31.5
9 Rated short circuit breaking times Times 30
10 Rated operation sequence   O-0.3s-CO-180s-CO
11 Mechanical life Circuit breaker (load switch) Times 10000
Three-position switch 5000
12 Rated insulation level 1min power frequency withstand voltage (effective value) Phase, to ground kV 42
Fracture 48
Lightning impulse withstand voltage (peak) Phase, to ground 75
Fracture 85
Power frequency withstand voltage of secondary circuit V 2000
13 Contact opening distance mm 9±1
14 Overtravel 3±0.5
15 Interphase center distance 210±1
16 Closing contact bounce time ms ≤2
17 Three phase asynchronous of opening ≤2
18 Opening time

 

When the operating voltage is

highest 17~55
rated
Minimum
19 Closing time ms 30~70
20 Average opening speed (first 6mm average) m/s 1.0~1.8
21 Average closing speed (after 6mm average) 0.8~1.4
22 Main conductive circuit’s resistance μΩ ≤100
23 Contact pressure N 3200±150
24 Opening contact’s rebound amplitude mm ≤2

VGK-I-12 series indoor high voltage AC vacuum circuit breaker

 

Hot products

Company profile

VGK Series Indoor High Voltage Vacuum Circuit Breaker used in Air insulated cabinet

VGK Series Indoor High Voltage Vacuum Circuit Breaker used in Air insulated cabinetVGK Series Indoor High Voltage Vacuum Circuit Breaker used in Air insulated cabinet

 

Certifications

VGK Series Indoor High Voltage Vacuum Circuit Breaker used in Air insulated cabinet 

Packing&transport

VGK Series Indoor High Voltage Vacuum Circuit Breaker used in Air insulated cabinet 

 

 

Contact us if you need more details on Vacuum Circuit Breaker. We are ready to answer your questions on packaging, logistics, certification or any other aspects about 10kv Vacuum Circuit Breaker、Air Insulated Cabinet Circuit Breaker. If these products fail to match your need, please contact us and we would like to provide relevant information.

Product Categories : VGK series > VGK circuit breaker